Parallel battery strings
Performing ohmic testing on parallel strings: Parallel strings present a challenge when performing ohmic testing. This is because a parallel battery string has multiple paths for the test current to flow. In a series string the injected test current only has one path, through the battery under test. Since the all the test current goes through the battery under test a proper repeatable measurement is made.