TTRU3

True three-phase transformer turns ratio tester

  • Guaranteed accuracy ±0.05 % from -20 °C to +50 °C
  • Three-phase test voltage - up to 250V
  • Three-phase step up ratio (patent pending)
  • Phase shifting and zigzag transformers tested easily and accurately
  • Smallest/lightest three-phase test set on the market
  • Fast three-phase tests - less than 10 seconds

Megger’s TTRU3 transformer turns ratio tester is a revolutionary instrument designed to perform three-phase turns ratio measurements using step-up excitation (patent pending). A single three-phase lead-set connection is all that is required to complete three-phase tests in less than 10 seconds!

The TTRU3 is capable of three-phase excitation and can induce up to 250 V on the primary winding, overcoming the voltage dependence seen on larger transformers. The three-phase source also allows you to test phase shifting and zigzag transformers, and provides you with a guaranteed accuracy of ±0.05 % from -20 °C to +50 °C.

What’s more, the TTRU3 can be connected to a computer, enabling you to download results or control the instrument remotely. There is also an optional 2 inch printer for the instrument, enabling you to have a hard copy of your results if required.

You can also configure test plans and store results directly on the TTRU3 using the built-in 7 inch (18 cm) daylight-viewable touch screen display. To generate reports, results can be downloaded in Excel, and PDF files can be saved to a USB drive. 

Last but not least, it’s also the smallest and lightest three-phase test set on the market!

Step up your transformer testing with TTRU3

Technical Documents
Technical guide
One touch OLTC with the TTRU3
Technical guide
Transformer turns ratio test: some unknown facts
Technical guide
TTRU3 - 1 phase vs 3 phase
Technical guide
TTRU3 - Magnetic Balance
Technical guide
TTRU3 - Step up vs Step down
Technical guide
TTRU3 Calibration verification
Technical guide
TTRU3 Factory ratio testing of power transformer
Technical guide
TTRU3 Phase Shifting Transformers
TTRU3 3.2.1

To upgrade from 2.2.4 to 3.x.x, the TTRU3 must be returned to a factory or ASC.

TTRU3 Release Notes
TTRU3-Release-Notes-3-2-1.pdf
380.1 KB | 20/06/22
TTRU3 PC Software
TTRU3_installer_3-2-1.exe
32.1 MB | 20/06/22
TTRU3 Embedded Software

** Once downloaded, the zip file must be extracted before copying the .mender file to the root of a thumb drive **

ttru3_update_3-2-1.zip
235.9 MB | 20/06/22
TTRU3 2.2.4
TTRU3 Release Notes
TTRU3-Release-Notes-2-2-4.pdf
186.3 KB | 05/04/22
TTRU3 PC Software
TTRU3_installer_2-2-4.exe
42.0 MB | 05/04/22
TTRU3 Embedded Software
 
** Once downloaded, the zip file must be extracted before copying the .gz file to the root of a thumb drive **
TTRU3_Embedded_2-2-4.zip
87.8 MB | 05/04/22
What is a Transformer Turns Ratio test?

A Transformer Turns Ratio (TTR) test checks that a transformer is converting energy in an expected way. The test is also known as simply a turns ratio test. A TTR test is performed by a ratio meter (ratio tester). This test validates the transformer design, the transformer nameplate, and the transformer’s fixed transforming abilities throughout its service life. A TTR test should be performed to confirm that the transformer’s de-energized tap changer is properly positioned and that shorted windings turns do not exist. The ratio meter provides convenient and accurate readings of power transformer ratios and polarities.

A Transformer Turns Ratio test works in accordance with the same fundamental electromagnetic phenomena that the transformer operates. The difference is that the TTR test typically uses a low voltage (LV) AC excitation signal (< 250 VAC) on a per-phase base or as a three-phase simultaneous excitation.

What is the difference between Transformer Turns Ratio (TTR), Transformer Nameplate Ratio (TNR), and Transformer Voltage Ratio (TVR)?

During a TTR test, one actually measures the TVR. Afterward, for three-phase transformers, a correction factor that depends on the vector configuration of the windings may need to be applied.

It is impossible to measure TTR from accessible points on a transformer. An assumption is made in TTR testing that, because of no-load conditions, the voltage ratio of a transformer (TVR) is equal to the turns ratio (TTR). This, of course, ignores the reality that a true no-load condition cannot be achieved for all winding configurations. Another assumption in TTR testing is that all the flux produced by one winding links with the second winding, ignoring leakage flux. These assumptions, for some transformers, result in ‘false positives’ when looking for problems in a conventional TTR analysis.

Finally, TNR is the ratio provided on a transformer’s nameplate, or one that can be calculated from the line-to-line winding voltages provided on the nameplate. In summary, the transformer turns ratio can be expressed as:

1.PNG

Is there any difference between single-phase turns ratio test and three-phase turns ratio tests?

Yes. Three-phase power transformers are often tested on a per-phase basis with a single-phase source, using relays to switch the power from one phase to another as necessary. Three-phase transformers are produced with a wide range of winding configurations and, in general, it is more difficult to test accurately if the LV winding is delta configured. This is because TTR testing assumes that the secondary winding is an open circuit and has no load connected. With a delta-connected LV winding and measurements performed on a per-phase basis, this assumption does not hold, as the winding under test is loaded by its connection with the other two windings in the delta loop. The current circulating in the delta loop leads to internal losses affecting the accuracy of the TTR measurement.

In these cases, it is recommended either to energize the HV winding line-to-line or to use three-phase excitation. Flux distribution will be more uniform, leading to a higher coupling between windings, so the results are less sensitive to excitation voltage. Excitation losses during the test are shared by all three sources, providing higher accuracy results as compared to those obtained with single-phase excitation. Simultaneous three-phase excitation reduces testing time and improves the efficiency of resources.